Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
---|---|
Place of Origin: | Henan in China |
Packaging Details: | carton box |
Quick Details
- Model Number: NA1000D
- Brand Name: Globeinstrument
Specifications
NA1000D Application: online monitoring alarm for hydrogen cooled generator in generator plant and hydrogen leakage in hydrogen plant with maximum 16 sensor units to centralized control the multipoint.
NA1000D Characteristics
Design special sampling system in accordance with the position of different measure points on-site do not transfer explosive and inflammable hazardous gas
The system with compact structure, it is easy to install, the instruments can directly indicate the hydrogen concentration of measure point. Online monitoring of instrument is stable and on-site workload of its maintenance is small.
NA1000D Technical Parameters:
NA1000D sensor (generator application) Monitoring range: 0 ~ 4.00% (0 ~ 100% LEL) Accuracy: ± 2% FS Explosion-proof grade: Exia Ⅱ C T3
Installation position: close bus, internal cold water tank, and the air side of oil return pipe in turbine side or exciter side, or cooler, etc
Measuring range | 0~4.00% (0~100%LEL) |
Accuracy | ±2%F.S |
Sampling method | Diffusion |
Environment temperature | -10°C~50°C |
Environment humidity | 0~98%RH |
Explosion-proof grade | ExiaⅡCT3 |
Working voltage | 24V DC Power 1W |