Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
---|---|
Place of Origin: | Guangdong in China |
Quick Details
- Application: Computer
- Type: On-line
Specifications
Features:
1. 1/2/3KVA in 2U, 6KVA in 3U
2.Double conversion
3.True Isolation technology offers the most complete power protection and highest quality power for all IT applications.
4. RS 232 management software
5.SNMP Slots for remote monitoring and control
6..load sensing, overload protection, dynamic by-pass, temperature monitoring software for preventative diagnostics.
7.LE/LCD option
8.Extended backup time capacity.
TECHNICAL SPECIFICATIONS:
Product Series |
Rack Mount 1~6kVA |
||||
Model |
R-C1K/C1KS |
R-C2KS |
R-C3KS |
R-C6KS |
|
Rated Power |
VA/W |
1kVA / 0.7kW |
2kVA / 1.4kW |
3kVA / 2.1kW |
6kVA/4.2kW |
Input |
Nominal Voltage |
220VAC |
|||
Voltage Range |
115 ~ 300VAC |
176 ~ 276VAC |
|||
Frequency Range |
46 ~ 54Hz(default), user adjustable within 40~60Hz |
46 ~ 54Hz |
|||
Power Factor |
0.97 |
0.98 |
|||
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
Terminal Block |
||
Output |
Voltage |
220VAC ± 2% |
220VAC ± 1% |
||
Frequency |
46~54Hz or 50Hz ± 0.2Hz (Line mode) 50Hz ± 0.2Hz ( Battery mode) |
46~54Hz (Line mode) 50Hz ± 0.05Hz ( Battery mode) |
|||
Waveform |
Sine Wave |
||||
Overload Capability |
108%~150% for 30 sec., 3150% for 300 ms |
105%~130% for 10 min., 3130% for 1 min. |
|||
Current Crest Ratio |
3:1 |
||||
Bypass |
Automatic Transfer |
on overload and UPS failure |
|||
Before UPS Power-on |
Default "NO", user adjustable to "YES" |
Yes |
|||
Voltage Range |
80~264VAC (Default), user adjustable within 80~286VAC |
176 ~ 261VAC |
|||
Output Connections |
IEC320 -10A * 4 |
IEC320-10A * 4 |
IEC320-10A and Terminal Block |
IEC320-10A * 4 and Terminal Block |
|
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and vice versa |
Zero |
|||
LED indicators |
Status |
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault |
|||
Audible Alarm |
Bypass, On battery mode, Battery low, Overload, Fault |
||||
Communications |
RS-232 Serial Interface |
||||
Intelligent Slot; OPTIONS: WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC) |
|||||
Network Surge Protection |
RJ45 I/O port available for network or Fax/Modem |
||||
Environmental |
Operating Temperature |
0 ~ 40°C |
|||
Operating Humidity |
20 ~ 90% non-condensing |
||||
Main Unit |
Net Weight (Kg) |
15.3 |
10.3 |
11.2 |
18.3 |
Dimensions (W x D x H) mm |
482.6 x 450 x 88 (2U) |
482.6 x 600 x 130 (3U) |
|||
Battery Pack |
Type |
Internal Batteries |
External Battery Pack |
||
Nominal DC Voltage |
36VDC |
96VDC |
240VDC |
||
Backup Time (Full load) |
5 min |
9 min (with 1 BP) |
5 min (with 1 BP) |
7 min (with 1 BP) |
|
Net Weight (Kg) |
-- |
25.3 |
58.2 |
||
Dimensions (W x D x H) mm |
-- |
482.6 x 450 x 88 (2U) |
482.6 x 600 x 130 |