Hebei Junai Power Technology Co., Ltd.
China Manufacturer with main products: Polymeric Surge Arrester, Isolator, Epoxy Fiberglass Rod, Composite Insulator, Bus Bar Insulator, Porcelain Insulator, Cut Out Fuse,... |
57-35KV Porcelain Line Post Insulator
FOB Price: | 2.50 - 19.00 USD/Acre |
---|---|
Shipping: | 30days |
Payment Terms: | L/C, T/T, D/A, D/P, Western Union, MoneyGram |
-
ECVV Safebuy Services
According to the requirements of buyers, ECVV.com will purchase the cost-effective Chinese products for you from the well-chosen suppliers database which was accumulated in the past 10 years.Learn More>>
-
Safebuy Service Guarantee
Provide financial security for multinational purchaser; Determine delivery time and acceptance product according to the purchasing requirements; Arrange Chinese export declarations and international logistics; Provide unified delivery of products from different suppliers.
Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
---|---|
Place of Origin: | Hebei in China |
Packaging Details: | Packed in carton and wooden case |
Quick Details
- Rated Voltage: 10KV-220 KV
- Application: High Voltage
- Material: Porcelain
- Type: Insulator
- Model Number: Porcelain Line Post Insulator
- Brand Name: JUNAI
- COLOR: BROWN
Specifications
Porcelain Line post insulator can be divided into horizontal line posts and vertical line posts according to insulator connectivity way, used for 6kV to 132kV transmission and distribution power lines. Porcelain Line post insulator made of porcelain materials, called line post porcelain insulator which installed with insulator stud. Line post insulator stud can be divided into long insulator stud and short insulator stud. Same dimension of the fittings as porcelain pin insulator, so they can be exchanged.
ANSI ceramic line post Insulators
1. ANSI 57-1, 57-2… series ceramic line post insulators drawings, technical data and images show as follows:
Type | ||||||||
Fig NO. | 1 | 2 | 3 | 4 | 5 | 5 | ||
Leakage distance | mm | 356 | 559 | 737 | 1016 | 1143 | 1346 | |
Dry arcing distance | mm | 165 | 241 | 311 | 368 | 438 | 489 | |
Cantilever strength | kN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | |
Power frequency flashover voltage | Dry | KV | 70 | 100 | 125 | 140 | 160 | 180 |
Wet | KV | 50 | 70 | 95 | 110 | 130 | 150 | |
Critical impulse flashover voltage | Positive | KV | 120 | 160 | 200 | 230 | 265 | 300 |
Negative | KV | 155 | 205 | 260 | 340 | 380 | ||
Radio interference voltage | Test voltage to ground | KV | 15 | 22 | 30 | 44 | 44 | 44 |
Max. RIV at 1 MHz | μV | 100 | 100 | 200 | 200 | 200 | 200 |
2. ANSI 57-12, 57-13… series ceramic line post insulators drawings, technical data and images show as follows:
Type | ||||||||
Fig NO. | 1 | 2 | 3 | 4 | 5 | 5 | ||
Creepage distance | mm | 356 | 559 | 737 | 1016 | 1143 | 1346 | |
Dry arcing distance | mm | 165 | 241 | 311 | 368 | 438 | 489 | |
Cantilever strength | KN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | |
Power frequency flashover voltage | Dry | KV | 70 | 100 | 125 | 140 | 160 | 180 |
Wet | KV | 50 | 70 | 95 | 110 | 130 | 150 | |
Critical impulse flashover voltage | Positive | KV | 120 | 160 | 200 | 230 | 265 | 300 |
Negative | KV | 155 | 205 | 260 | 340 | 380 | ||
Radio interference voltage | Test voltage to ground | KV | 15 | 22 | 30 | 44 | 44 | 44 |
Max. RIV at 1 MHz | μV | 100 | 100 | 200 | 200 | 200 | 200 |
3. ANSI 57-21, 57-22… series ceramic line post insulators drawings, technical data and images show as follows:
Type | ||||||||
Fig No. | 1 | 2 | 3 | 4 | 5 | 5 | ||
Creepage distance | mm | 356 | 559 | 737 | 1016 | 1143 | 1346 | |
Dry arcing distance | mm | 165 | 241 | 311 | 368 | 438 | 489 | |
Cantilever strength | KN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | |
Power frequency flashover voltage | Dry | KV | 70 | 100 | 125 | 140 | 160 | 180 |
Wet | KV | 50 | 70 | 95 | 110 | 130 | 150 | |
Critical impulse flashover voltage | Positive | KV | 120 | 160 | 200 | 230 | 265 | 300 |
Negative | KV | 155 | 205 | 260 | 340 | 380 | ||
Radio interference voltage | Test voltage to ground | KV | 15 | 22 | 30 | 44 | 44 | 44 |
Max. RIV at 1 MHz | μV | 100 | 100 | 200 | 200 | 200 |
200 |
4. ANSI 57-31, 57-32… series ceramic line post insulators drawings, technical data and images show as follow:
Type | ||||||||
Creepage distance | mm | 356 | 559 | 737 | 1016 | 1143 | 1346 | |
Dry arcing distance | mm | 165 | 241 | 311 | 368 | 438 | 489 | |
Cantilever strength | KN | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | |
Power frequency flashover voltage | Dry | KV | 70 | 100 | 125 | 140 | 160 | 180 |
Wet | KV | 50 | 70 | 95 | 110 | 130 | 150 | |
Critical impulse flashover voltage | Positive | KV | 120 | 160 | 200 | 230 | 265 | 300 |
Negative | KV | 155 | 205 | 260 | 340 | 380 | ||
Radio interference voltage | Test voltage to ground | KV | 15 | 22 | 30 | 44 | 44 | 44 |
Max. RIV at 1 MHz | μV | 100 | 100 | 200 | 200 | 200 | 200 |
Africa porcelain line post type Insulators
1. Capless line post insulator, the main technical parameters:
Type: | |||||||
Nominal voltage | KV | 22 | 22 | 22 | 33 | 33 | 33 |
Nominal creepage distance | mm | 630 | 750 | 750 | 900 | 1120 | 1120 |
Bottom fixing diameter | mm | M20 OVERSIZE | M20 OVERSIZE | M20 OVERSIZE | M20 OVERSIZE | M20 OVERSIZE | M20 OVERSIZE |
Top fixing diameter | mm | 73 | 73 | 73 | 73 | 73 | 73 |
Top groove radius | mm | 20 | 20 | 20 | 20 | 20 | 20 |
Cantilever strength | KN | 4 | 4 | 10 | 6 | 10 | 4 |
Dry arcing distance | mm | 290 | 325 | 325 | 389 | 390 | 415 |
Power frequency flashover dry | KV | 124 | 109 | 111 | 161 | 105.7 | 137.1 |
Power frequency flashover wet | KV | 84 | 86 | 85 | 123 | 86.4 | 101.1 |
Power frequency withstand dry | KV | 121 | 106 | 106 | 146 | 96 | 131.1 |
Power frequency withstand wet | KV | 76 | 72 | 69 | 85 | 76 | 88.4 |
Impulse withstand voltage (bil) | KV | 183 | 184 | 186 | 230 | 207 | 229.7 |
Impulse flashover positive | KV | 187 | 191 | 193 | 238 | 221.5 | 241.3 |
Impulse flashover negative | KV | 362 | 343 | 344 | 410 | 418.4 | 414.6 |
2. Capped line post insulator, the main technical parameters:
Type | ||||||||||
Nominal voltage | KV | 11 | 11 | 12 | 33 | 33 | 33 | 33 | 33 | 33 |
Nominal creepage distance | mm | 300 | 405 | 400 | 786 | 1050 | 813 | 1100 | 900 | 1116 |
Bottom fixing diameter | mm | M20 | M20 | M20 | M20 | M20 | M20 | M20 | M20 | M20 |
Top fixing diameter | mm | 73 | 73 | 73 | 73 | 73 | 73 | 73 | 73 | 73 |
Top groove radius | mm | 12.5 | 25 | 12.5 | 25 | 25 | 20 | 20 | 25 | 25 |
Cantilever strengh | KN | 7 | 12.5 | 4 | 4 | 12.5 | 10 | 10 | 10 | 12.5 |
Dry arcing distance | mm | 160 | 170 | 218 | 320 | 390 | 335 | 425 | 368 | 432 |
Power frequency flashover dry | KV | 70 | 79.7 | 97 | 131 | 157 | 123 | 140 | 125 | 140 |
Power frequency flashover wet | KV | 40 | 43.7 | 65 | 87 | 106 | 87 | 91 | 95 | 110 |
Power frequency withstand dry | KV | 63 | 75.1 | 91 | 127 | 145.9 | 115 | 124 | 110 | 120 |
Power frequency withstand wet | KV | 35 | 38 | 57 | 75 | 87.6 | 72 | 82 | 78 | 90 |
Impulse withstand voltage (bil) | KV | 100 | 95 | 150 | 205 | 247 | 192 | 245 | 200 | 215 |
Impulse flashover positive | KV | 110 | 142.8 | 164 | 209 | 258.4 | 197 | 255 | 210 | 230 |
Impulse flashover negative | KV | 183 | 218.2 | 263 | 346 | 413.7 | 370 | 414 | 260 | 280 |