Shanghai Echu Wire & Cable Co., Ltd.
China Manufacturer with main products: Lift Cable, Crane Cable, Electrical Cable, Traveling Cable, Control Cable, PVC Insulated Cable, Flexible Cable, Pedant Cable |
Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
---|---|
Place of Origin: | Shanghai in China |
Packaging Details: | rolls |
Quick Details
- Insulation Material: Special PVC
- Conductor Material: Copper
- Application: Power Station
- Brand Name: ECHU/OEM
- Type: H05VVC4V5-K
- Jacket: PVC
- Model Number: H05VVC4V5-K
Specifications
these cables are used for flexible application for medium mechanical stress with free movement, but without tensile stress or forced movements in dry, moist and wet areas. these cables are not suitable for open air use. They are designed for application in measuring, controling, cutting tools and assembly lines. these cables were tested according to DIN VDE 0207 and 0473 and were approved to be fully resistant to oils and are not effected by chemical influences. Cables for moist and wet areas, particularly used for machines in breweries, bottling plants as well as car washing stations.
Stranded bare copper core according to DIN VDE 0295 and IEC 60228 cl. 5
Core insulation of special PVC TI2 according to DIN VDE 0281 part 1
Cores stranded in layers, black cores with repeated white numbering according to DIN VDE 0293
Green-yellow earth core in the outer layer, from 3 cores and more
Inner sheath of special PVC according to DIN VDE 0281 part 1
Screening of tinned copper wires, approx. Coverage 85%
Outer sheath of special PVC TM5 according to DIN VDE 0281 part 1, HD 21.1S2/A16, color grey
PVC self-extinguishing and flame-retardant, according to DIN VDE 0482 part 265-2-1/ EN 50265-2-1/ IEC 60332-1
Technical data
Control cable with special PVC outer sheath, resistant to oils according to DIN VDE 0281 part 13, HD 21.13 S1 and IEC 60227/74
Temperature range flexing from -5C to +70C; fixed from -40C to +70C
Nominal voltage Uo/U 300/500 V
Spark test 6000 V
Test voltage a.c. Core/core 2000 V 5 min; core/screen 2000 V 5 min
Insulation resistance min. 20 M x km
Minimum bending radius approx. 10 x cable diameter
Radiation resistance up to 80 x 106 cJ/kg (up to 80 Mrad)